The Infinit-E range is an optional three-phase all-electric water heater for predominantly commercial hot water applications.
The electric storage water heaters is designed with flexibility in mind as it is fitted with between one and six titanium elements. The KW rating within the Infinit-e range is scalable from 12kw to 72kw ensuring that our appliances are suitable for a wide variety of applications.
The cylinder is manufactured with stainless steel adding durability and enabling extensive warranties. The use of stainless steel also makes the Infinit-E range lightweight and easily manoeuvrable when compared to glass-lined variants.
The empty weight of the Infinit-e is 54kg maximum. Another added feature is that all electrical elements can be fitted to a single-phase supply, should site limitations dictate. Each element within the appliance range has its own controllable thermostat with a temperature range of between 49 and 90 degrees Celsius, all elements are fuse protected and there is no need for expensive sacrificial anodes thanks to the tough stainless-steel build.
InfinitE12 | InfinitE24 | InfinitE36 | InfinitE48 | InfinitE60 | InfinitE72 | ||
Electrical.Data | |||||||
Input | kW | 12 | 24 | 36 | 48 | 60 | 72 |
Elements | - | 1 | 2 | 3 | 4 | 5 | 6 |
Element Material | Titanium | ||||||
Power Supply | VAC/ Hz | Single phase / three phase / 400(-15/+10%)/50 (+1HZ) 230(-15/+10%) | |||||
General | |||||||
Empty Weight | kg | 54 | |||||
Maximum Weight | kg | 350 | |||||
Storage Capacity | l | 305 | |||||
Maximum Working Pressure | kPa (bar) | 600 (6) bar | |||||
Draw off (Tcold/Tset = Tmax) | |||||||
1st hour flow rate @ 44°C rise (l/hr) | l/h | 540 | 775 | 1010 | 1245 | 1479 | 1714 |
Continuous flow rate @44 C rise (l/hr) | l/h | 235 | 470 | 705 | 940 | 1174 | 1409 |
Storage Recovery @44 rise in Min | Min | 78 | 39 | 26 | 19 | 16 | 13 |
1st hour flow rate @ 50°C rise (l/hr) | l/h | 512 | 718 | 925 | 1132 | 1338 | 1545 |
Continuous flow rate @50 C rise (l/hr) | l/h | 206.7 | 413.4 | 620.1 | 826.8 | 1033.5 | 1240.2 |
Storage Recovery @50 rise in min | Min | 89 | 44 | 30 | 22 | 18 | 15 |
1st hour flow rate @ 55°C rise (l/hr) | l/hr | 493 | 681 | 869 | 1057 | 1245 | 1432 |
Continuous flow rate @55 C rise (l/hr) | l/h | 187.9 | 375.8 | 563.7 | 751.6 | 939.5 | 1127.4 |
Storage Recovery @55 rise | Min | 97 | 49 | 32 | 24 | 19 | 16 |